Fire Alarm Control Panel IQ8Control C / M
42
FB 798951.10.GB0 / 04.15
Connection of the AC mains voltage and emergency power supply
For connecting the mains voltage (230 V AC) and emergency power supply, see Chapter 4.1.
N
L1
U
X2
Mains
230V~
Fig. 32: Connection of the AC mains voltage and batteries
Disconnect all power from the panel before carrying out any installation work! Observe before
connecting the AC mains voltage (e.g. 230 V AC) the specifications given on the panels nameplate
(adhesive label) inside the housing.
Connection terminals
removable
Fig. 33: Connection terminals removable
Observe permitted torque (max. 0.4 Nm) of
the terminals!
DIL Switch S2
S2
OFF
Normal operation
Position "OFF" (factory setting)
S2
ON
Service mode
Position "ON“
The LED V50 lits for an optical indication
The service mode will be activated after a panel reset and displayed at
the
operation
panel.
Reset Button S1
S1
Reset
Press the RESET button to restart the panel. Alarm and fault messages are reset, all
detector zones and primary loops are switched on and all changed switch settings are
read in.
A panel cold start using the RESET button is only possible when the housing contact (panel
housing) is open. If the panel interface was connected to the USB input, the connection is
detected only after a reset.