Battery Monitor Module (Pat No. 788051.10)
The battery monitor module is inserted between the 12 V battery to be monitored and the associated connection
contact of the basic module of the FACP.
Please see the documentation (Part No. 798253.10)
for installation as well as for additional information
about the battery monitor module “BatMon 12”.
Fig. 26: Battery monitor module - overview
Mounting
Rückseite / Rearside
1
2
2
Up to 2 batteries may be place inside the
compact housing FACP IQ8Control C.
Place batteries as shown and insert fastener.
The module is fastened to the batteries using
the enclosed hook-and-loop strip.
Adhere one part of the hook-and-loop strip to
the back side of the module
and the other
part to the batteries
, then line up the two
parts of the strip and fasten the module in
place.
Fig. 27: Mounting in the compact housing FACP IQ8Control C
Rückseite / Rearside
7
8
Up to 2 batteries 12 V / 24 Ah may be placed
inside the lower housing part of the FACP IQ8
Control M or in the extension housing
(Part No. 783000 / 01).
Place batteries as shown and insert fastener.
The module is fastened to the batteries using
the enclosed hook-and-loop strip.
Adhere one part of the hook-and-loop strip to
the back side of the module
and the other
part to the rear wall of the housing
, then
line up the two parts of the strip and fasten
the module in place.
Fig. 28: Mounting in the housing of the FACP IQ8Control M or in the extension housing
Damage to the system!
Please note that depending on the rechargeable batteries used, a significant weight must be
supported by the fastening screws of the extension housing. It is not permissible to install the
rechargeable batteries without these fastening clamps.
Use only the enclosed connector cable. The use of other cables or extensions is prohibited!
Only use a T 4 A fuse in order to ensure reverse polarity protection.
Ensure the correct polarity (+/-) when connecting the cable! The battery monitor cable is not
suitable for connecting a 24 V DC emergency power supply!
The battery monitor modules “BatMon 12” (Part No. 788051.10) can be installed in existing
IQ8Control fire alarm control panels.
Each battery requires one module.