Fire Alarm Control Panel IQ8Control C / M
60
FB 798951.10.GB0 / 04.15
Operating mode 2
Relay K1 positive switching, not monitored
+
12
V
DC Ub
in
t.
K1
C
NC
NO
BA
C
K
GN
D
K1
BR8
BR7
BR6
1
2
3
1
2
3
1
2
3
Relay K1
Positive switching (+12 V DC
intern
/ max. 1 A),
not monitored
Fig. 51: Terminal of the master box relay K1
Operating mode 3
Relay K1 not monitored change-over contact
K1
BA
C
K
GND
K1
C
NC
NO
BR8
BR7
BR6
1
2
3
1
2
3
1
2
3
Relay K1
Potential-free, not monitored change over
contact
External voltage < 30 V DC, max. 1 A
Fig. 52: Terminal of the master box relay K1
The IQ8Control FACP's relays may only be connected to DC voltages. No AC voltage may be
applied, not even when a relay is programmed as a >non-monitored change-over contact<.
Observe permitted torque (max. 0.4 Nm) of the terminals!