Fire Alarm Control Panel IQ8Control C / M
FB 798951.10.GB0 / 04.15
119
Trouble
Code No.
Possible Cause
1st. measure
2nd. measure
069
There are more detectors on the
loop than programmed in the
customer data.
If this change is not desired,
connect service PC and run
a wiring recognition. Re-
program customer data.
If this change is not desired,
connect service PC and run a
wiring recognition. Re-program
customer data.
070
Error during detector data
allocation.
Perform detector data
assignment again.
---
080
This detector change may only
be performed with the service PC
because this detector required
customer data that cannot be
generated in the FACP itself.
If this change is not desired,
connect service PC and run
a wiring recognition. Re-
program customer data.
---
081
The detector has been replaced
with an OTI-detector. The sensor
type has changed in comparison
with the customer data.
Check whether detector type
change is desired; if it is,
activate loop.
Otherwise install detector you
require and re-start >Detector
change<
082
The detector has been replaced
with an OT-detector. The sensor
type has changed in comparison
with the customer data.
Check whether detector type
change is desired; if it is,
activate loop.
Otherwise install detector you
require and re-start >Detector
change<
083
The detector has been replaced
with an I-detector. The sensor
type has changed in comparison
with the customer data
Check whether detector type
change is desired; if it is,
activate loop
Otherwise install detector you
require and re-start >Detector
change<
084
The detector has been replaced
with a TM-detector. The detector
type has changed in comparison
with the customer data.
Check whether detector type
change is desired; if it is,
activate loop.
Otherwise install detector you
require and re-start >Detector
change<
085
The detector has been replaced
with a TME-detector. The
detector type has changed in
comparison with the customer
data.
Check whether detector type
change is desired; if it is,
activate loop.
Otherwise install detector you
require and re-start >Detector
change<
086
The detector has been replaced
with a TD-detector. The detector
type has changed in comparison
with the customer data.
Check whether detector type
change is desired; if it is,
activate loop.
Otherwise install detector you
require and re-start >Detector
change<
087
The detector has been replaced
with an O-detector. The detector
type has changed in comparison
with the customer data.
Check whether detector type
change is desired; if it is,
activate loop.
Otherwise install detector you
require and re-start >Detector
change<
088
Detector circuitry has been
changed at detector location.
Now detector has neither external
circuit (relay / LED) nor isolating
relay.
If this change is desired,
connect service PC and run
a wiring recognition.
Re-program customer data.
---