Fire Alarm Control Panel IQ8Control C / M
66
FB 798951.10.GB0 / 04.15
7 Micro
module
The FACP IQ8Control C / M has a modular design, so that micro modules can be replaced/extended at any time.
Only remove or insert micro modules when the FACP is voltage free.
Switch off the power and battery supply.
Wait at least 10 seconds before the micro modules are replaced or supplemented.
Take suitable measures to discharge static electricity.
Check correct installation (micro modules and connection cables).
Switch on the power and battery supply.
If necessary, check/supplement the customer data using the programming software tools
8000.
7.1 Loop
modules
The following two loop modules are available for the Fire Alarm Control Panel
IQ8
Control C/M:
esserbus
®
loop module (Part No.
78
4382 /
78
4382.10 /
78
4382.D0)
To connect fire detectors series 9200 and IQ8Quad as well as esserbus
®
transponders. To operate this loop
module, the loop voltage on the power supply module (Part No. 802426) must be set to 27.5 V with the relevant
jumper.
esserbus
®
PLus loop module (Part No.
80
4382 /
80
4382.10 /
80
4382.D0)
Fire Alarm Control Panels IQ8Control C/M with esserbus
®
PLus are based on the standard esserbus
®
functionality
with the additional function to connect and power audible alarm devices directly to the loop. For this operation of
the loop module it is necessary to set the loop voltage of the Power supply module (Part No.802426) with the
appropriate jumper to 42 V. The audible alarm devices connected to esserbus
®
PLus are supplied by the loop
voltage and do not need an external power supply.
Basic data on loop of esserbus
®
and
esserbus
®
PLus
Less than 127 loop devices or 127 zone isolators per loop
Loop may be divided into 127 individual detector zones (customer data programming)
No more than 32 fire detectors per detector zone
Capability of combining loop and spur loop operation. No sub-spur branching!
Recommended type of cable for loop:
Use clearly identified communications cable I-Y (St) Y n x 2 x 0.8 mm or fire alarm cable!
Max. impedance of the loop incl. spur measured with respect to the load factor for IQ8Quad fire detectors:
max. 3500 m
1)
.
For cable diameter with 0,8 mm and a max. Loop resistance of 130
(measured from terminal A+ to B+).
Max. 8 communications transponder per loop
max. 16 communications transponder per FACP
max. 32 esserbus
®
transponders per loop.
max. 100 esserbus
®
transponders per FACP
OR
max. 32 Smoke aspirating systems TITANUS PRO / TOP SENS
®
EB per loop.
max. 100 Smoke aspirating systems per FACP.
1)
see table chapter 7.1.3.
Damage to the system!
It is only possible to operate the esserbus
®
PLus devices compatible with the higher loop voltage
(42 V DC). Mixed operation of Standard and esserbus
®
PLus function within one FACP is not
possible! Loop devices compatible with esserbus
®
PLus (transponders, detectors MCP´s etc.)
are identified by the Part No. 80xxxx.
These 80xxxx devices are also fully compatible to the existing devices with Part No. 78xxxx and
may be used in standard esserbus
®
installations.