Input
Calibration -
Minimum
and Maximum Range Values
Release M
DR4500A Classic Series Circular Chart Recorder With or Without Control Product Manual
179
April 2017
Sensor Type
PV Input Range
PV Input Range
0%
100%
milliAmps
4 to 20 mA
4 mA
20 mA
milliVolts
0 to 10 mV
0 mV
10 mV
10 to 50 mV
10 mV
50 mV
Volts
0 to 5 V
0 V
5 V
0 to 10 V **
0 V
10 V
Radiamatic
(RH)
1400.00 to 3400.00
760.00
to 1871.11
0.99 mV
57.12 mV
*Range values for thermocouples are based on a cold junction temperature of 32°F (0°C). These values must be
adjusted for the actual cold junction temperature when using the ambient temperature method for calibrating
thermocouple inputs.
**Resistor network 30755232-002 must be installed in inputs #1 and #2 when using this range, see set up diagram