Configuration Parameter Definitions
Chart Parameters Set Up Group
88
DR4500A Classic Series Circular Chart Recorder With or Without Control Product Manual
Release M
April 2017
4.4 Chart Parameters Set Up Group
Introduction
The functions listed in this group deal with how the chart will be set up.
CAUTION
Before making any configuration changes to the “Chart” Set Up group, place the recorder in
“Chart Hold”. Press the
CHART
key to stop the chart rotation. Press again after configuration
entry is made.
Chart group prompts
Table 4-3 lists all the function prompts in the chart parameters setup group and their definitions.
Table 4-3 Chart parameters group definitions
Lower Display
Prompt
Upper Display
Range of Setting or Selection
Parameter Definition
CHRTSPD
8HR
12HR
24HR
7DAYS
XHR
CHART SPEED
— This is the time it will take to drive
the chart one complete revolution.
8 Hour revolution
12 Hour revolution
24 Hour revolution
7 Day revolution
X hour revolution - make Hours per Revolution selection
at prompt “HOUR/REV”.
HOUR/REV
1 to 744 Hours
HOURS PER REVOLUTION
— Set the desired chart
speed. Appears only if XHR was selected at prompt
“CHRT SPD”.
LINEARIZ
LINEAR
NONLIN
LINEARIZATION