
Setpoint
Ramp/Soak Programming and Operation -
Setpoint
Program Event Set Up Group
Release M
DR4500A Classic Series Circular Chart Recorder With or Without Control Product Manual
169
April 2017
To ensure control of relay by segment event
To make sure a segment event operates the associated relay, observe the requirements below.
Table 6-7 Segment event relay operation requirements
Relay
Relay is controlled by (in order of priority)
Requirements for operation of
relay by segment event
1
13.
Timer function
14.
Alarm 1
Do not configure Timer.
Configure Alarm 1 type
Event.
2
Alarm 2
Configure Alarm 2 type Event.
3
15.
Controller 1 output algorithms Relay Simplex,
Position Proportional, Relay Duplex,
Current/Relay Duplex
16.
Alarm 3
Do not configure Controller
#1 with these output
algorithms.
Configure Alarm 3 type
Event.
4
17.
Controller 1 output algorithms Position
Proportional, Relay Duplex, Current/Relay
Duplex
18.
Alarm 4
Do not configure Controller
#1 with these output
algorithms.
Configure Alarm 4 type
Event.
5
19.
Controller 2 output algorithms Relay Simplex,
Position Proportional, Relay Duplex,
Current/Relay Duplex
20.
Alarm 5
Do not configure Controller
#2 with these output
algorithms.
Configure Alarm 5 type
Event.
6
21.
Controller 2 output algorithms Position
Proportional, Relay Duplex, Current/Relay
Duplex
22.
Alarm 6
Do not configure Controller
#2 with these output
algorithms.
Configure Alarm 6 type
Event.