Operation
-
Using
Two Sets of Tuning Constants (PID Values)
Release M
DR4500A Classic Series Circular Chart Recorder With or Without Control Product Manual
137
April 2017
Table 5-20 Procedure for setting switchover values
Step
Operation
Press
Action/Result
1
Select switchover value
function
FUNC
assuming you
are still in Set Up
group CONTROL
Until you see:
Upper Display:
The switchover value
Lower Display:
SW VALUE
▲
or
▼
Select the switchover value in the upper display.
Set Tuning constant values for each set
There are specific tuning constants that must be set for each set. The procedure in
Table 5-21 shows you
how to access these constants and change their values.
Table 5-21 Procedure for setting tuning constant values
Step
Operation
Press
Action/Result
1
Select Tuning Set Up
group
SET
UP
Until you see:
Upper Display:
SET UP
Lower Display:
TUNING
2
Select the tuning
constants
FUNC
Successively displays the following constants:
Upper Display:
Tuning constant value
Lower Display:
PROPBD
or
GAIN*
RATEMIN*
RSETMIN
or
RSETRPM*
PROPBD2
or
GAIN2**
RATE2MIN**
RSET2MIN
or
RSET2RPM**
*PIDSET1
– will be used when PV or SP, whichever is
selected, is
greater
than the switchover value.
**PIDSET2
– will be used when PV or SP, whichever is
selected, is
less
than the switchover value.
▲
or
▼
Change the value of any of the above listed prompts in
the lower display.