Operation
-
Resetting
and Displaying Totalizer Value
144
DR4500A Classic Series Circular Chart Recorder With or Without Control Product Manual
Release M
April 2017
5.13 Resetting and Displaying Totalizer Value
Introduction
If the totalizer is enabled and has been configured to allow resetting, you can reset the current totalizer
value as follows.
Refer to
Section 3 - Configuration
, under Set-up prompt “TOTAL 1” for Input #1 or “TOTAL 2” for
Input #2 to enable the totalizer function and allow the totalizer to be reset.
Refer to the procedures that follow to:
reset the totalizer locally,
reset the totalizer externally (switch),
display the totalizer value.
Resetting the totalizer
Table 5-27 to reset the totalizer value.
Table 5-27 Procedure for resetting the totalizer
Step
Operation
Press
Action/Result
1
Access the Totalizer Set
Up group
SET
UP
Until you see:
Upper Display:
SET UP
Lower Display:
TOTAL 1
or
TOTAL 2
2
Allow Totalizer Reset
FUNC
once
You will see:
Upper Display:
Ex XXX
Lower Display:
(a value)
FUNC
again
You will see:
Upper Display:
NO
Lower Display:
RSET TOT
▲
or
▼
Change NO to YES in the upper display.
ATTENTION
Function prompt “RSETABLE” must
be set to “LOCAL”.
3
Return to normal
operation
LOWR
DISP
Returns to normal operation.
External totalizer reset
The totalizer can be reset to “0” from external switch #1 or external switch #2. Refer to
Subsection 3.9 –
Totalizer Set Up Group
and set function prompt “RSETABLE” to “EXT SW1” or “EXT SW2”.