Configuration Parameter Definitions
Control Parameters Set Up Group
98
DR4500A Classic Series Circular Chart Recorder With or Without Control Product Manual
Release M
April 2017
Lower Display
Prompt
Upper Display
Range of Setting or Selection
Parameter Definition
OUT1ALG
The
OUTPUT ALGORITHM
lets you select the type of
output you want.
ATTENTION
If the recorder has two controllers
(both enabled), OUT1ALG applies for controller #1 and
OUT2ALG applies for controller #2.
Selections are model dependent. For example, current
output models cannot be configured for Time
Proportioning Simplex Output.
TIME
RELAY SIMPLEX
— type of output using one SPDT
relay. Its normally open (NO) or normally closed (NC)
contacts are selected by positioning an internal jumper.
Other prompts affected: "OUT HYST"
Controller #1 uses Relay 3 and overrides control of
relay by Alarm 3. Controller #2 uses Relay 5 and
overrides control of relay by Alarm 5.
CURRNT
CURRENT SIMPLEX
— type of output using one 4 to
20 mA signal that can be fed into a positive or negative
grounded load of 0 to 1000 ohms. The signal can be
recalibrated for any desired range from 3.25 to 21 mA
for 0 to 100% output.
POSITN
POSITION PROPORTIONAL SIMPLEX
— type of
output using two SPDT relays and a motor which has a
100 to 1000 ohms feedback slidewire.
Other prompt affected: "DEADBAND"
Controller #1 uses Relays 3 and 4 and overrides
control of relays by Alarms 3 and 4. Controller #2
uses Relays 5 and 6 and overrides control of relays
by Alarms 5 and 6.
TIME D
RELAY DUPLEX
— type of output using two SPDT
relays. Its normally open (NO) or normally closed (NC)
contacts are selected by positioning an internal jumper
(see Installation section).
Other prompts affected: "DEADBAND"
Controller #1 uses Relays 3 and 4 and overrides
control of relays by Alarms 3 and 4. Controller #2
uses Relays 5 and 6 and overrides control of relays
by Alarms 5 and 6.
CUR TI
CURRENT/RELAY DUPLEX (RELAY = HEAT)
is a
variation of duplex with current active for 0 to 50%
output (tuning set 2) and relay active for 50 to 100%
output (tuning set 1).
Other prompts affected: "4-20 RNG," "DEADBAND"
Controller #1 uses Relay 3 and overrides control of
relay by Alarm 3. Controller #2 uses Relay 5 and
overrides control of relay by Alarm 5.