Configuration Parameter Definitions
Alarms Set Up Group
108
DR4500A Classic Series Circular Chart Recorder With or Without Control Product Manual
Release M
April 2017
Lower Display
Prompt
Upper Display
Range of Setting or Selection
Parameter Definition
AxS1 H L
H I
LO
ALARM x SETPOINT 1 STATE
— select whether you
want the alarm type chosen in prompt "AxS1TYPE" to
alarm high or low or the beginning or end of a segment
in setpoint Ramp/Soak programming.
HI ALARM
–
Relay coil is de-energized when the PV is
above
the setpoint.
LO ALARM
– Relay coil is de-energized when the PV is
below
the setpoint.
AxS1SCAL
1
10
100
1000
10000
100000
1E6
MULTIPLIER FOR ALARM TYPE “TOTAL”
SELECTION
— the alarm is only a high value. Enter a
scaler of from 1 to 1000000.
(Base value x multiplier = alarm setpoint value)
AxS2 H L
H I
LO
ALARM x SETPOINT 2 STATE
— select whether you
want the alarm type chosen in prompt "AxS2TYPE" to
alarm high or low or the beginning or end of a segment
in setpoint Ramp/Soak programming.
HI ALARM
LO ALARM
AxS2SCAL
1
10
100
1000
10000
100000
1E6
MULTIPLIER FOR ALARM TYPE “TOTAL”
SELECTION
— the alarm is only a high value. Enter a
scaler of from 1 to 1000000.
(Base value x multiplier = alarm setpoint value)
ALx HYST
0.0 to 100.0% of span or full
output as appropriate
ALARM HYSTERESIS
— an adjustable hysteresis is
provided on each alarm such that when the alarm is
OFF it activates at exactly the alarm setpoint; when the
alarm is ON, it will not deactivate until the variable is
0.0% to 100.0% (whatever has been set) away from the
alarm setpoint.
Configure the hysteresis of the alarms based on
INPUT signals as a % of input range span.
Configure the hysteresis of the alarm based on
OUTPUT signals as a % of the full scale output
range.
Repeat this procedure for Alarm 2, Alarm 3, Alarm 4, Alarm 5, Alarm 6 configuration.