the upgrade process.
l
If you do not select the Interactive mode , the firmware will be
upgraded directly after the transfer. The controller will be
stopped without any prompt.
4.
Click
Proceed with Upgrade
to continue.
5.
From the
Release Number
list, select the target release module. The
target firmware version is displayed.
6.
Click
Next
. The target firmware name, state and version are
displayed.
7.
Click
Next
to transfer and upgrade the firmware.
8.
After the boot firmware is upgraded, enter the password to re-
connect the controller. The application firmware is transferred and
upgraded.
9.
After the application has been upgraded, enter the password to re-
connect the controller.
10.
The firmware upgrades.
11.
Perform the relevant procedures for ControlEdge 2020 controller
and ControlEdge 900 controller.
l
For ControlEdge 2020 controller:
a.
Click
OK
. The primary CPM synchronizes the firmware with the
secondary CPM, and upgrades the firmware of the secondary
CPM automatically.
b.
To check whether the secondary CPM upgrade is complete,
click
Connect
from the Home Page and check that the
Firmware version
is the same as the primary CPM.
l
For ControlEdge 900 controller:
l
Upgrading the previous release to R150
a.
Connect to the secondary CPM (slot B).
b.
Repeat Step 1 to Step 10 to upgrade the firmware on the
secondary CPM.
l
Upgrading R150 to the later release
a.
Click
OK
. The primary CPM synchronizes the firmware with
the secondary CPM, and upgrades the firmware of the
secondary CPM automatically.
74
Chapter 5 - Operating