Protocol Description
Timeout, system regards it has already received a
complete data frame.
The default value is 0 which means this option is
disabled.
l
Max Length (Bytes)
: The maximum number of bytes
for a data frame, ranging from 0 to 532. If the length
of a received data frame exceeds the Max Length,
system regards it has already received a complete
data frame.
The default value is 0 which means this option is
disabled.
l
End Delimiter (Hex)
: Configured special characters in
hexadecimal and based on bytes validates if a data
frame is sent completely. If the received data frame
has same characters with the End Delimiter, system
regards it has already received a complete data
frame.
The default setting is blank which means this option
is disabled.
For how to configure User Defined protocol, see
"User Defined Protocol" in the
ControlEdge Builder
Function and Function Block Configuration
Reference
.
7.
Click
Save
to complete the configuration.
Configuring a controller simulator
Controller simulator can be deployed on a Virtual Machine, and
enables the user to configure a controller without connecting a
physical controller.
For this release, the controller simulator does not support I/O
communication.
52
Chapter 4 - Software