9.
After the application has been upgraded, enter the password to re-
connect the controller.
10.
Click
OK
to complete the firmware upgrade.
Upgrading firmware for a redundant controller
ATTENTION: It is recommended to upgrade the firmware
without opening a project.
There are two procedures for the firmware upgrade of an redundant
controller.
n
On-process
: The primary CPM is synced with the secondary CPM.
ATTENTION: On-process is ONLY applicable for upgrading
R150 to later release firmwares.
n
Off-process
: The primary CPM is not synced with the secondary
CPM.
For ControlEdge 900 Controller, it is ONLY allowed in
Stopped,
Running
or
Stop Locked
operating mode.
You can rotate the mode switch on CPM to change the operating
mode, see "CPM mode switch" in
ControlEdge 900 Platform
Hardware Planning and Installation Guide
. If the mode switch is in
the REMOTE position, See "Setting operating modes" on page 1
for more information.
Prerequisites
n
Assume the primary CPM is at slot A and the secondary CPM is at
slot B.
n
Both primary (slot A) and secondary (slot B) CPMs are powered
on.
To upgrade the firmware with On-process procedure
ATTENTION: For ControlEdge 2020 controller, on-process
procedure is ONLY applicable for a standalone redundant
controller without EFM configured and IOM connected.
1.
From the Start Page, click
Connect
to connect the target primary
CPM (slot A).
2.
From the Home Page, select
Upgrade Firmware
under
Maintenance
,
72
Chapter 5 - Operating