CHAPTER
8
SECURITY
Logon feature
To prevent unauthorized access to a running system, ControlEdge
Builder supports three user types including Operator, Engineer and
Administrator, and this user management controls the operating
privileges. A password is required when operating as a specific user
type connecting to a running controller. The default password of each
user type is listed as follows:
User Name
Password
Operator
Oper@123
Engineer
Engr@123
Administrator
Admin@123
It is recommended to changed the passwords periodically. It is also
recommended to share the passwords with only the minimum
required people, who need to perform configuration operations on
ControlEdge 900 controller and ControlEdge 2020 controller.
For more information, see “User Privileges” in the
ControlEdge
Builder User’s Guide
.
Setting operating modes
The operating modes for the CPM are:
n
(Only apply to ControlEdge 900 Controller)
Stop Locked
: All tasks
are inactive and ready to be executed, therefore the I/O channels
hold last value and no output signals are transmitted to the I/Os.
n
(Only apply to ControlEdge 900 Controller)
Run Locked
: CPM
performs all control and communication tasks and on-line
configuration editing and configuration changes are inhibited.
n
Running
: CPM performs all control and communication tasks and
on-line configuration editing are permitted.
n
Stopped
: All tasks are inactive and ready to be executed, therefore
119