controller will warm start in
Running
mode. If the warm start
fails, the controller will go to
Stopped
mode.
n
Last operating mode, or Stopped after an abnormal stop
This option is the default setting for ControlEdge 900 controller.
The controller will start in the operating mode that it was last in
prior to a power off, unless there was an abnormal stop caused by
a system error such as a watchdog timeout issue. It will then start
in
Stopped
mode.
l
If the controller was in
Running
mode before power off, the
controller will warm start in
Running
. If the warm start fails, the
controller will go to
Stopped
mode.
l
If the controller was stopped manually before power off, the
controller will start in
Stopped
mode.
l
If the controller was stopped abnormally before power off, the
controller will start in
Stopped
mode.
n
Running
The controller will warm start in
Running
mode. If the warm start
fails, the controller will go to
Stopped
mode.
n
Stopped
The controller will start in
Stopped
mode.
ATTENTION: If you reboot the controller manually, the
configuration in this section will not take effect. For example: If
you select
Running
here, and you select
Reboot Controller
under
Maintenance
, and click
Cold Reboot
. The controller will perform
cold start, but not warm start after it reboots.
Configuring controller redundancy
To disable redundancy
1.
Under
Controller and Programming
, select
Configure Controller
Redundancy
.
2.
Select
Disable Controller Redundancy
to disable the redundancy
function.
3.
Click
OK
. Redundancy has been disabled. The IP address
configured for the secondary controller will be disabled.
To enable redundancy
46