59
1.
Click
IEC Programming Workspace
from the toolbar, or from Home
Page, click
Program with IEC61131-3
.
2.
From the
Project Tree Window
, right-click
Data Type
and select
Insert
>
Datatypes
and name the target data type.
3.
Double-click the newly added data type, you can edit it in the text
editor.
For I/O_DataTypes, each I/O Channel has one or two structures. All of
the related information for this channel is grouped together in the
structures as shown below. You can use this information as reference
for I/O channel configuration and programming.
Table 4-3: I/O channel structures of the I/O_DataTypes
Structure type
Parameter
Parameter type
ANALOG_INPUT_TYPE
STS
USINT
PV
REAL
EUHI
REAL
EULO
REAL
EUHIEX
REAL
EULOEX
REAL
ANALOG_OUTPUT_TYPE
OP
REAL
ANALOG_OUTPUT_READBACK_
TYPE
STS
USINT
OP_READBACK
REAL
EUHI
REAL
EULO
REAL
EUHIEX
REAL
EULOEX
REAL
DIGITAL_INPUT_TYPE
STS
USINT
PV
BOOL
DIGITAL_OUTPUT_TYPE
OP
BOOL
Chapter 4 - Software