GSMBR / iGSMBR Installation and Setup Guide
4-2
Register using the Programming Tool
The interactive registration feature allows the installer to register the module through a
series of keyboard commands on the 7720P Programming Tool. This method of registration
lets the installer monitor the registration process.
Registering …
Once the installation is complete, press the [Shift] and the up arrow
[
½
] key. The registration message is sent and the unit waits for the
acknowledgment.
Registration
SUCCESS
If this is a new installation and the city, central station, and
customer numbers have been correctly entered, the module is
registered and this message is displayed.
The communications module is now in full service and
available for alarm reporting to the central station.
Possible Errors
Registration BAD
Timed Out
Displayed if no response to the registration request is received.
Registration BAD
Pri Sub ID BAD
Indicates the city, central station, or customer number for the labeled
account(s) is not accepted. The ID information was either entered
incorrectly, or the central station failed to pre-authorize programmed
ID numbers with AlarmNet customer service.
Registration BAD
2
nd
Sub ID BAD
Indicates the city, central station, or customer number for the
Secondary account is not accepted. The ID information was either
entered incorrectly, or the central station failed to pre-authorize
programmed ID numbers with AlarmNet customer service.
Registration BAD
Pri&Sec – IDs BAD
Displayed when both primary and secondary subscriber IDs are
invalid.
Registration BAD
Pri ID – Need PIN
Displayed if this is a repair/replacement, or an error was made in
programming the Primary account information for an existing
account. This prompt appears for 2 seconds. See the
Replacing an
existing module
section below for further displays.
Registration BAD
2
nd
ID – Need PIN
This prompt is displayed if this is a repair/replacement, or an error
was made in programming the Secondary account information for an
existing account. This prompt appears for 2 seconds. See the
Replacing an existing module
section below for further displays.
Registration BAD
Pri&2
nd
– Need PIN
This prompt is displayed if this is a repair/replacement, or an error
was made in programming BOTH the Primary and Secondary
account information for an existing account. This prompt appears for
2 seconds. See the
Replacing an existing module
section below for
further displays.
Summary of Contents for AlarmNet GSMBR
Page 2: ......
Page 38: ...GSMBR iGSMBR Installation and Setup Guide 3 22 ...
Page 50: ...GSMBR iGSMBR Installation and Setup Guide A 2 ...
Page 54: ...GSMBR iGSMBR Installation and Setup Guide C 2 ...
Page 57: ...NOTES ...
Page 58: ...NOTES ...
Page 59: ...NOTES ...
Page 60: ...NOTES ...
Page 61: ...NOTES ...
Page 62: ...NOTES ...