Section 3: Programming
3-11
4204 Emulation Mode Options
For control panels that do not support LRR-ECP communication, the 4204 Emulation modes
provide a means of sending up to eight unique reports based on defined system conditions.
In 4204 mode, the communications module functions as a logical 4204 Relay Module, where
each relay number, referred to in the module as zone number, can be programmed to send a
report based on the output function programmed in the control for that relay. Each relay-
zone can also be programmed to send a restore message of the reported condition, can be set
to delay transmission of messages, and can be programmed to send reports only when a
conditional zone is triggered (armed), (see
Important Information Regarding
Zone Input
Options
later in this section).
In single 4204 mode, the module supports up to four relay-zones. In Two-4204 mode, the
module functions as two 4204 modules, supporting up to eight relay-zones.
Refer to the following table.
4204 Relay Outputs map to zones
First 4204 Zones
(device address entered in Prompt 14)
:
Second 4204 Zones
(device address entered in Prompt 14, plus 1)
:
Relay 1 = Zone 1
Relay 2 = Zone 2
Relay 3 = Zone 3
Relay 4 = Zone 4 or conditional zone trigger if
“report only if armed” is selected in any zone 1-3
when using single 4204 mode.
NOTE:
Zone 4 status is not reported when being
used as the conditional (armed) trigger zone.
Relay 1 = Zone 5
Relay 2 = Zone 6
Relay 3 = Zone 7
Relay 4 = Zone 8 or conditional zone trigger if
“report only if armed” is selected in any
zone 1-7 when using Two-4204 mode.
NOTE:
Zone 8 status is not reported when being
used as the conditional (armed) trigger zone or if
tamper reporting is enabled.
When using the module in 4204 Emulation Mode, DO NOT enable the Long-Range Radio
module in control panel programming. Instead, enable 4204 relay module address(es) and
program the appropriate relay activation functions for the relay-zones being used. In some
control panels, it is called “relay programming” and in others it is called “output device
programming.” It is recommended that “close and stay closed” (usually choice 2) action is
selected. Selection of momentary activation will cause the communications module to
generate an alarm and NOT a restore, even if the module is programmed to send a restore for
the given zone.
In 4204 mode, messages are reported in ADEMCO High-Speed format. Zone alarms
(status 7) are reported with “1” (alarm) or “3” (restore) displayed in the zone position for the
respective zone (e.g. alarm on zone 2: 5155 5555 7; restore 5355 5555 7). A supervision fault
trouble message is automatically sent if the module detects no activity on its connection to
the control. The message is: 5555 5515 5; restore message is: 5555 5535 5.
Refer to Table 5 for 4204 Emulation Mode programming and follow the prompts that pertain
to 4204 or Two-4204 mode. A check mark (
) indicates whether the prompt applies to that
mode.
Programming
Press the [ENTER] key to begin programming
and
f
ollow the prompts for the mode of
operation being programmed.
NOTE:
The central station can remotely block access to local device
programming. If this has been done, the following prompt appears:
Access to Prog
Mode Denied
Summary of Contents for AlarmNet GSMBR
Page 2: ......
Page 38: ...GSMBR iGSMBR Installation and Setup Guide 3 22 ...
Page 50: ...GSMBR iGSMBR Installation and Setup Guide A 2 ...
Page 54: ...GSMBR iGSMBR Installation and Setup Guide C 2 ...
Page 57: ...NOTES ...
Page 58: ...NOTES ...
Page 59: ...NOTES ...
Page 60: ...NOTES ...
Page 61: ...NOTES ...
Page 62: ...NOTES ...