7847i/7847i-E Installation and Setup Guide
6-2
Redir 2
Service OK
The service at AlarmNet Control on Redir 2 is
functioning. See below for possible errors that may
occur at this stage of testing.
Testing Redir 3
The first step of the test traces the connection to Redir 3
at AlarmNet Control.
Testing Redir 3
Reached Redir 3
A successful trace to Redir 3 is indicated here. See
below for possible errors that may occur at this stage of
testing.
Reached Redir 3
Testing Service
After a successful trace
to
Redir 3, a test of the service
at
Redir 1 is performed. That is, the first test determines if
a message can reach AlarmNet Control; this test
determines if the connection point (Redir) at AlarmNet
Control knows what to do with the message once it
receives it.
Redir 3
Service OK
The service at AlarmNet Control on Redir 3 is
functioning. See below for possible errors that may
occur at this stage of testing.
RDR1 RDR2 RDR3
OK OK OK
A summary of the tests is displayed after Redir 3 is
tested. The example shows that the tests of all three
connection points, or Redirs, were successful. If an error
occurred at any point, the summary will display “FAIL”
under the faulty Redir.
Possible Errors Running Network Diagnostics
Errors may occur at either while tracing the connection to a given Redir or while testing the
service at a given Redir. The following list highlights the most common errors. Please
contact the AlarmNet Technical Assistance Center (TAC) for help regarding any errors NOT
listed below:
Possible Errors
Testing Redir
x
FAIL before Gtwy
While tracing the connection to Redir
x
, the trace fails
before ever reaching the local gateway (router).
Testing Redir
x
FAIL at Gtwy
While tracing the connection to Redir
x
, the trace fails
after reaching the local gateway (router).
Testing Redir
x
FAIL at Pvt IP
While tracing the connection to Redir
x
, the trace fails
after reaching the private IP.
Testing Redir
x
FAIL on IP Addr
While tracing the connection to Redir
x
, the trace fails
after reaching the public IP.
Redir
x
ERR:Proxy 18
After a successful trace to Redir
x
, the test of the service
timed out without a response.
Summary of Contents for AlarmNet 7847i-E
Page 2: ......
Page 14: ...7847i 7847i E Installation and Setup Guide 2 6 ...
Page 42: ...7847i 7847i E Installation and Setup Guide 5 4 ...
Page 52: ...7847i 7847i E Installation and Setup Guide B 2 ...
Page 56: ...7847i 7847i E Installation and Setup Guide D 2 ...
Page 57: ...NOTES ...
Page 58: ...7847i 7847i E Installation and Setup Guide NOTES ...
Page 59: ...NOTES ...
Page 60: ...7847i 7847i E Installation and Setup Guide NOTES ...
Page 61: ...NOTES ...
Page 62: ...7847i 7847i E Installation and Setup Guide NOTES ...