Section 2: Mounting and Wiring
2-3
LYNXR-I CONTROL PANEL
7847i-E-018-V0
GND
ECP DATA OUT
ECP DATA IN
V+
RED
NC
BLK
GRN
YEL
RED
BLK
GRN
YEL
+12 VDC
GND
D
ATA
I
N
D
A
T
A
OUT
4
5
6
3
4-WIRE CABLE (N4632-4)
TB1
7847i / 7847i-E
Figure 4. Wiring a LynxR-I for ECP Mode
Wiring for Zone Trigger Mode
To trip the zone on the 7847i/7847i-E in V+ trigger mode, the positive triggering voltage from
the control panel must be within 2.0V-14V.
Trigger levels above this range may cause permanent damage to the unit.
Trigger levels below this range result in unreliable operation.
To trip the zone on the 7847i/7847i-E in V- trigger mode, the negative triggering voltage
must be less than 1.0V.
NOTE:
LynxR and LynxR-EN have a designated trigger for V- trigger.
Connect a wire from the triggering source (bell output, voltage trigger, etc.) of the control
panel to the zone input of the module, and connect a common ground between the module
and control panel.
UL
The configurations shown in Figures 5a and 5b have not been evaluated by UL.
Examples of zone connections are shown below:
CONTROL PANEL
7847i-E-020-V0
GND
BELL (+)
+12 V
GND
ZONE INPUT Z1/Z2
V+
( )
(+)
4
5
3
TB1
7847i / 7847i-E
Figure 5a. Wiring the 7847i/7847i-E Zone 1 Input for a Positive (+) Triggered Bell Output
CONTROL PANEL
7847i-E-021-V0
GND
BELL ( )
+12 V
GND
ZONE INPUT Z1/Z2
V+
( )
(+)
4
5
3
TB1
7847i / 7847i-E
Figure 5b. Wiring the 7847i/7847i-E Zone 1 Input for a Ground (-) Triggered Bell Output
Summary of Contents for AlarmNet 7847i-E
Page 2: ......
Page 14: ...7847i 7847i E Installation and Setup Guide 2 6 ...
Page 42: ...7847i 7847i E Installation and Setup Guide 5 4 ...
Page 52: ...7847i 7847i E Installation and Setup Guide B 2 ...
Page 56: ...7847i 7847i E Installation and Setup Guide D 2 ...
Page 57: ...NOTES ...
Page 58: ...7847i 7847i E Installation and Setup Guide NOTES ...
Page 59: ...NOTES ...
Page 60: ...7847i 7847i E Installation and Setup Guide NOTES ...
Page 61: ...NOTES ...
Page 62: ...7847i 7847i E Installation and Setup Guide NOTES ...