Section 4: Registration
4-3
Possible Errors When Configured for AlarmNet-i
Registration BAD
Timed Out
Displayed if no response to the registration request is
received.
Registration BAD
Pri Sub ID BAD
Indicates the city, central station, or customer number
for the Primary account(s) is not accepted. The ID
information was either entered in error, or the central
station failed to pre-authorize programmed ID numbers
with AlarmNet customer service.
Registration BAD
2nd Sub ID BAD
Indicates the city, central station, or customer number
for the Secondary account is not accepted. The ID
information was either entered in error, or the central
station failed to pre-authorize programmed ID numbers
with AlarmNet customer service.
Registration BAD
Pri&Sec
IDs BAD
Displayed when both Primary and Secondary subscriber
IDs are invalid.
Registration BAD
Pri ID – Need PIN
Displayed if this is a repair/replacement, or an error was
made in programming the Primary account information
of 7847i/7847i-E
for an existing account. This prompt
appears for 2 seconds. See the
Replacing an existing
module
section below for further displays.
Registration BAD
2nd ID – Need PIN
Displayed if this is a repair/replacement, or an error was
made in programming the Secondary account
information of 7847i/7847i-E
for an existing account.
This prompt appears for 2 seconds. See the
Replacing
an existing module
section below for further displays.
Registration BAD
Pri&2nd – Need PIN
Displayed if this is a repair/replacement, or an error was
made in programming BOTH the Primary and
Secondary account information of 7847i/7847i-E
for an
existing account. This prompt appears for 2 seconds.
See the
Replacing an existing module
section below for
further displays.
Replacing an existing module using the programming tool
Enter PIN#
This prompt appears after pressing the
down arrow [
↓↓↓↓
]
on the 7720P.
NOTE:
If it is necessary to exit registration mode, press
ESC from the 7720P programming tool.
Enter a 4-digit alphanumeric PIN number provided by
an authorized AlarmNet representative.
Press the [ENTER] key.
Registering …
The registration message is sent and the unit waits for
acknowledgement.
Registration
SUCCESS
If the PIN is valid, the new 7847i/7847i-E
is registered
and the old unit unregistered. Additionally, AlarmNet
sends a substitution alarm to the central station.
Summary of Contents for AlarmNet 7847i-E
Page 2: ......
Page 14: ...7847i 7847i E Installation and Setup Guide 2 6 ...
Page 42: ...7847i 7847i E Installation and Setup Guide 5 4 ...
Page 52: ...7847i 7847i E Installation and Setup Guide B 2 ...
Page 56: ...7847i 7847i E Installation and Setup Guide D 2 ...
Page 57: ...NOTES ...
Page 58: ...7847i 7847i E Installation and Setup Guide NOTES ...
Page 59: ...NOTES ...
Page 60: ...7847i 7847i E Installation and Setup Guide NOTES ...
Page 61: ...NOTES ...
Page 62: ...7847i 7847i E Installation and Setup Guide NOTES ...