7847i/7847i-E Installation and Setup Guide
3-10
transmission of messages, and can be programmed to send reports only when a conditional
zone is triggered (armed), (see
Zone Input Options
later in this section).
In single 4204 mode, the unit
supports up to four relay-zones. In two-4204 mode, the unit
functions as two 4204 modules, supporting up to eight relay-zones.
4204 Relay Outputs map
to 7847i/7847i-E
zones as follows:
First 4204 Zones
(device address entered in Prompt 23)
:
Second 4204 Zones
(device
address entered in Prompt 23, plus 1)
:
Relay 1 = Zone 1
Relay 2 = Zone 2
Relay 3 = Zone 3
Relay 4 = Zone 4 or conditional zone trigger if
“report only if armed” is selected in
any zone 1-3 when using single 4204
mode.
NOTE:
Zone 4 status is not reported when
being used as the conditional (armed) trigger
zone.
Relay 1 = Zone 5
Relay 2 = Zone 6
Relay 3 = Zone 7
Relay 4 = Zone 8 or conditional zone trigger if
“report only if armed” is selected in
any zone 1-7 when using two-4204
mode.
NOTE:
Zone 8 status is not reported when
being used as the conditional (armed) trigger
zone or if tamper reporting is enabled.
When using the 7847i/7847i-E
in 4204 Emulation Mode, DO NOT enable the Long-Range
Radio module in control panel programming. Instead, enable 4204 relay module address(es)
and program the appropriate relay activation functions for the relay-zones being used. In
some control panels, it is called “relay programming” and in others it is called “output device
programming.” It is recommended that the “close and stay closed” (usually choice 2) action is
selected. Selection of momentary activation will cause the unit
to generate an alarm and NOT
a restore, even if the unit
is programmed to send a restore for the given zone.
In 4204 mode, messages are reported in ADEMCO High-Speed format. Zone alarms (status
7) are reported with “1” (alarm) or “3” (restore) displayed in the zone position for the
respective zone (e.g. alarm on zone 2: 5155 5555 7; restore 5355 5555 7). A supervision fault
trouble message is automatically sent if the module detects no activity on its connection to
the control. The message is: 5555 5515 5; restore message is: 5555 5535 5.
Refer to Table 5 for 4204 Emulation Mode programming and follow the prompts that pertain
to 4204 or Two-4204 mode. A check mark (
✔
) indicates whether the prompt applies to that
mode.
Alternative Mode Programming
Press the [ENTER] key to begin programming
and
f
ollow the prompts for the mode of
operation being programmed.
NOTE:
The central station can remotely block access to
local device programming. If this has been done,
the following prompt appears:
Access to Prog
Mode Denied
Table 5: Programming a 7847i/7847i-E for Zone Trigger, 4204 Emulation, or Two-4204 Emulation modes.
PROMPTS
ZONE
TRIG.
4204/
2-4204
ENTRY
OPTIONS
DESCRIPTION
1
Strt Prog Mode?
Y/N_
✔
✔
[Y], [N]
Enters programming mode.
2
Enter Password
✔
✔
[0-9, A-F, N,
S, T, X, Y]
If a password has been previously assigned, this
prompt appears.
Enter a 4-digit password (0-9, A-F, N, S, T, X, Y).
The next prompt appears.
3
Program Device?
Y/N_
✔
✔
[Y], [N]
To begin programming the module, press [Y] and
go to Prompt 9: "Device Mode."
To create a password if none has been assigned,
press [N] and go to Prompt 4: Create Password.
To change an existing password, press [N] and go
to Prompt 5: "Change Password."
Summary of Contents for AlarmNet 7847i-E
Page 2: ......
Page 14: ...7847i 7847i E Installation and Setup Guide 2 6 ...
Page 42: ...7847i 7847i E Installation and Setup Guide 5 4 ...
Page 52: ...7847i 7847i E Installation and Setup Guide B 2 ...
Page 56: ...7847i 7847i E Installation and Setup Guide D 2 ...
Page 57: ...NOTES ...
Page 58: ...7847i 7847i E Installation and Setup Guide NOTES ...
Page 59: ...NOTES ...
Page 60: ...7847i 7847i E Installation and Setup Guide NOTES ...
Page 61: ...NOTES ...
Page 62: ...7847i 7847i E Installation and Setup Guide NOTES ...