VISTA-120 Installation and Setup Guide
5-10
1*24
Cross Zoning Pair Three
Enter
001-128
Enter
000,000
to disable
Select the third pair of cross zones, which must both be faulted within a five-
minute period to cause an alarm.
1*25
Cross Zoning Pair Four
Enter
001-128
Enter
000,000
to disable
Select the fourth pair of cross zones, which must both be faulted within a five-
minute period to cause an alarm.
1*26
Panic Button or Speedkey
00
= panic function (for D key = not used)
01-32
= macro number
Select for the A, B, and C keys whether the system performs a panic or a
speedkey function when the key is pressed.
Select for the D key whether the system performs a speedkey function or is
not used.
1*27
Field 1*31 RF Transmitter Check-in
interval to be Multiple of 1 Hour or 2
Hours
0
= 2-Hours
1
= 1 Hour
Select whether the programming of field 1*31 should be in 1 hour or 2 hour
increments (must be 1 hour for CENELEC compliance).
1*28
RF Transmitter Low Battery Sound
0
= disarmed state only
1
= both armed and disarmed states
Select when the RF transmitter low-battery condition should display and
audible beep annunciate on the keypad.
1*29
RF Transmitter Low Battery
Reporting
0
= disable
1
= enable
If enabled, the system sends a Trouble message for RF transmitter low-
battery condition to the central station.
NOTE:
The Trouble message will be sent for a transmitter supervision failure,
independent of this selection.
1*30
RF Receiver Supervision Check-in
Interval
Enter
02-15
times 2 hours (4-30 hours).
00
= disable receiver supervision.
Select the check-in monitoring interval for the RF receiver(s).
Failure of a receiver to receive any RF signal within the time entered results in
the activation of the response type programmed for zone 990 for the first
receiver and zone 988 for the second receiver and their related
communication reports.
1*31
RF Transmitter Check-in Interval
Enter
02-15
times 2 hours (4-30 hours).
00
= disable transmitter supervision.
Select the check-in monitoring interval for the RF transmitters.
Failure of an individual transmitter to send a supervision signal within the time
entered will result in a trouble response and related communication report.
1*32
Access Control Dialer Enables
0
= disable
1
= enable
There are six entries for this field as follows: Trace, Trouble, Not Used,
Bypass, System, Alarm.
If Trace is enabled, access grant/denial events are sent to the central station.
For the other events, if enabled, a report is sent to the central station.
1*33
Multifrequency Dialling with Pulse
Dial Back-up
0
= disable
1
= enable
If enabled, the communicator switches to decadic dial pulses if it is not
successful on the first attempt using multifrequency.
1*34
Communicator Split Reporting
Selection
0
= Split Reporting disabled
1
= Alarm, Alarm Restore, and Cancel
reports to primary, all others to secondary
2
= Open/Close and Test reports to
secondary, all other reports to primary
3
= Fire Alarms and Fire Restores to
primary, all other reports to secondary
Select the type of split reporting for system communication.
NOTE:
See *51 for split/dual reporting combinations.
1*35
Low Battery Test Interval
0
= 13 second test every 4 minutes (ANPI
requirement)
1
= 1.5 second test every 50 seconds
(Norwegian requirement)
Select the interval that the system performs a test of the system battery.
FIELD
TITLE and DATA ENTRIES
EXPLANATION
Summary of Contents for ADEMCO VISTA-120
Page 2: ...ii ...
Page 18: ...VISTA 120 Installation and Setup Guide 2 8 ...
Page 70: ...VISTA 120 Installation and Setup Guide 5 16 ...
Page 88: ...VISTA 120 Installation and Setup Guide 7 4 ...
Page 90: ...VISTA 120 Installation and Setup Guide 8 2 ...
Page 100: ...VISTA 120 Installation and Setup Guide A 2 ...
Page 104: ......
Page 106: ......
Page 113: ......