5-1
S E C T I O N 5
Data Field Descriptions
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
About Data Field Programming
The following pages list this control’s data fields in numerical order. Field numbers are listed in the left column, followed
by a “Title and Data Entries column, which lists the valid entries for each field. Experienced installers can simply follow
this column when programming the data fields. The “Explanation” column provides explanatory information and special
notes where applicable.
NOTE:
Refer to the
Programming Guide
for the default values. They are not listed in this section.
Use the
Programming Guide to record the data for this installation.
Programming Data Fields
Data field programming involves making the appropriate entries for each of the data fields. Start Data Field programming by entering the
installer code + 8 + 0 + 0 + 0.
FIELD
TITLE and DATA ENTRIES
EXPLANATION
*00
Installer Code
Enter 4 digits,
0-9
The Installer Code is a 4-digit code reserved for installation company use.
This is the only code that can be used to enter the Program Mode from the
keypad. This code cannot be used to disarm the system if it isn’t used to arm
the system. This code cannot be used to re-enter Program Mode if Program
Mode is exited by the *98 command.
*01
Master to Enable Installer
0
= disable
1
= enable
If enabled, the Master Code + OFF keying opens a 15-second time period in
which the Installer Code can be used (Norwegian requirement).
*03
Final Contact Set
0
= disable
1
= enable
If enabled, the exit delay will be infinitely long and the system will arm 5
seconds after the Zone Type 01 exit door opens and closes or closes if
already open and that condition was allowed prior to arming.
*04
Auto-bypass Exit Route Faults
0
= disable
1
= enable
If enabled, auto-bypass of unsealed burglary zones after 2
nd
attempt to arm
within 15 seconds after arming is rejected and the open zones are displayed
(Swedish Requirement).
*05
Arm with Low Battery
0
= disable (ANPI requirement)
1
= enable
If enabled, the user can arm the partition or system with a system low battery
present.
*06
Zone Type 5 Always Alarm
0
= disable
1
= enable
If enabled, a fault of a type 5 zone (tamper) causes a full alarm in any arming
mode (disarmed or armed).
If disabled, a fault of a type 5 zone (tamper) causes a trouble in the disarmed
state and a full alarm in any armed state.
*07
Allow Arming With Faults in Exit
Route
0
= disable
1
= enable
If enabled, allows arming with zone faults present in any of the exit route
zones (zone types 1, 2, 4, and 10), wherein a fault remaining in any of these
zone types at the end of the exit delay will result in a burglary alarm. (For
STAY/INSTANT arming, this applies to zone types 1 and 2 only.)
Automatic bypass of the zones is achieved (instead of alarm) if field 1*20 is
also enabled.
Summary of Contents for ADEMCO VISTA-120
Page 2: ...ii ...
Page 18: ...VISTA 120 Installation and Setup Guide 2 8 ...
Page 70: ...VISTA 120 Installation and Setup Guide 5 16 ...
Page 88: ...VISTA 120 Installation and Setup Guide 7 4 ...
Page 90: ...VISTA 120 Installation and Setup Guide 8 2 ...
Page 100: ...VISTA 120 Installation and Setup Guide A 2 ...
Page 104: ......
Page 106: ......
Page 113: ......