OPERATION
Voltage Selector Switch
Disconnect or turn OFF all appliances or tools connected to the
generator before changing the voltage selector switch position.
The generator may be damaged if the switch position is changed with
loads connected and operating.
The power available to each receptacle depends on the position of the
voltage selector switch.
120 V ONLY Position
When the voltage selector switch is in the 120 V ONLY position, you do not
need to spread the load over the receptacles. You must, however, make
sure the load on any receptacle does not exceed its available power shown
in the preceding table and the total load does not exceed 45.8 amps.
120 V/240 V Position
When the voltage selector switch is in the 120 V/240 V position, you
must balance the load. Divide the load between the two sets of
receptacles shown below. Balancing is necessary because each set of
receptacles is powered by only one power producing circuit that can
produce a maximum of 22.9 amps.
Switch Position
Receptacle
Available Power
120 V ONLY
①
30 A at 120 V
②
20 A at 120 V
③
20 A at 120 V
30 A at 120 V
None
120 V/240 V
①
22.9 A at 120 V
②
20 A at 120 V
③
20 A at 120 V
-
22.9 A at 240 V
Set of
Receptacles
Total Current
Available
Power Producing
Circuit
①
+
③
+
22.9 A
1
②
+
22.9 A
2