HV350 Mini Frequency Inverter User Manual
110
=0
,
forward jog stop
bit3
=1
,
reverse jog start
=0
,
reverse jog stop
bit4
0-
》
1
,
Fault reset command
bit5
reserved
bit6
=1
,
free stop command
=0
,
no command
bit7
=1
,
decrease stop command
=0
,
no command
BYTE8
reserved
ED
End byte
A0H
,
one byte
SUM
Xor check
Xor form BYTE1
to
BYTE9
2.
A message from the inverter to the computer
BYTE0
BYTE1
BYTE2
BYTE3
BYTE4
BYTE5
BYTE6
BYTE7
BYTE8
BYTE9
BYTE10
HD
AD
CT
OP
DT
ST
ED
SUM
Item
Byte name
Detail
HD
Start byte
02H
,
one byte
IN
address
Inverter address
,
one byte
,
0 is broadcast address
CT
Parameter operation status
One bye
0
:
success
1
:
data received is exceed the range
2
:
address is exceed the range
3
:
data can not be modified while inverter is running
4
:
data is read only, can not be modified
OP
Parameter number
Parameter number
,
two bytes
,BYTE3
is lower byte
,BYTE4
is higher
byte
DT
Parameter value
Parameter value
,
two bytes
,BYTE5
is lower byte
,BYTE6
is higher
byte
ST
Status word
Status word of the inverter
,
two bytes
,
BYTE7
is lower
byte
,
BYTE8
is higher byte.
Bits of BYTE7
are defined as following:
bit0
=1
,
forward run
=0
,
reserse run
bit1
=1
,
inverter fault
=0
,
inverter no fault