HV350 Mini Frequency Inverter User Manual
98
1:
When undervoltage occurs during running, fault relay acts and fault code
will be saved. When undervoltage occurs during stop state, fault relay
does not act, and fault code will not be saved.
2:
When undervoltage occurs in running or stopping state, fault relay acts
and fault code will be saved.
Pd.14 reserved
Setting range
:
0
~
1
Pd.15 reserved
Setting range
:
0
~
1
Pd.16
Under voltage point
Setting range
:
360
~
440
Default value is 400v (DC voltage). In some case when the input voltage is low or not stable,
the value can be adjusted to avoid under voltage fault.
PE Factory reserved
PE.00
~
PE.05
are reserved parameters for individual consumer.
PF Factory reserved
PF.00
~
PF.19
are reserved parameters for individual consumer.
PH Display function
PH.00
running
display
parameters
selection
Setting range
:
0
~
14
HV350 drive has 15 state parameters in running state. User can scroll through
them by pressing ►► key during running process. Function code PH.00 defines
the default display parameter after starting, which includes:
0: Frequency setting
1: Running frequency
2: Output current
3: Output voltage
4: Bus voltage
5: Overload rate
6: Preset line speed
7: Running line speed