HV350 Mini Frequency Inverter User Manual
71
P6.04 Selecting the function of control terminal X3 Setting range:0
~
30
P6.05 Selecting the function of control terminal X4 Setting range:0
~
30
P6.06 Selecting the function of control terminal X5 Setting range:0
~
30
P6.07 Selecting the function of control terminal X6 Setting range:0
~
30
P6.08 reserved
Setting range:0
~
30
Control terminals X1~X6 are programmable digital input terminals. X1~X6
can be defined by setting the values of P6.02~P6.07 respectively.
Programmable digital input terminal can be selected as ― no function‖
repeatedly (that is, it can be set as 0 at the same time). Function description is
shown below:
Content
Function
Content
Funtion
0
X1~X5: No function (can be selected
repeatedly)
16
Free run to stop
1
Run FWD
17
Three-wire control
2
Run Rev
18
Voltage/current switching
3
External reset
19
Input terminal for recording
program operation
4
Jog FWD (JOGF)
20
Start traverse operation
5
Jog REV (JOGR)
21
DC braking command
6
Multi-frequency 1
22
Acc/Dec disabled command
7
Multi-frequency 2
23
Switch between panel control
mode and external terminal
control mode
8
Multi-frequency 3
24
Counter trig signal
9
Multi-frequency 4
25
Counter reset signal
10
Terminals for selecting
Acc/Dec time 1
26
PID dormancy waking up