P2.06~P2.08 define the jog running parameters, which is shown in Fig. 8-7.
In Fig. 6-7, f1 is Jog running frequency (P2.08), t1 is Jog Acc time (P2.06), t3 is Jog Dec
time (P2.07), and t2 is the Jog running time.
Jog running command can be issued through panel, control terminal or host computer.
Fig. 6-7 Jog running parameters
P2.09 Multi-frequency 1
Setting range: 0~400.0Hz
P2.10 Multi-frequency 2
Setting range: 0~400.0Hz
P2.11 Multi-frequency 3
Setting range: 0~400.0Hz
P2.12 Multi-frequency 4
Setting range: 0~400.0Hz
P2.13 Multi-frequency 5
Setting range: 0~400.0Hz
P2.14 Multi-frequency 6
Setting range: 0~400.0Hz
P2.15 Multi-frequency 7
Setting range: 0~400.0Hz
P2.16 Multi-frequency 8
Setting range: 0~400.0Hz
P2.17 Multi-frequency 9
Setting range: 0~400.0Hz
P2.18 Multi-frequency 10
Setting range: 0~400.0Hz
P2.19 Multi-frequency 11
Setting range: 0~400.0Hz
P2.20 Multi-frequency 12
Setting range: 0~400.0Hz
P2.21 Multi-frequency 13
Setting range: 0~400.0Hz
P2.22 Multi-frequency 14
Setting range: 0~400.0Hz
P2.23 Multi-frequency 15
Setting range: 0~400.0Hz
Multi-frequency/speed is set in P2.09
~
P2.23, which can be used in multi-speed
running and programming state.
There are 15 multi-frequency operation modes, which can be selected through control
terminals.
Assumption:
―1 (ON)‖ means that control terminal is connected;
―0 (OFF)‖ means that control terminal is disconnected.
If control terminals of multi-frequency are not set, or all of them are in OFF position,
frequency setting is determined by function code P0.02;
If certain control terminal of multi-frequency is not in OFF position, frequency setting
is determined by function code P2.09~P2.23;
If multi-frequency operation is selected, Starting/stopping the drive is determined by
control mode selection P0.01.