HV350 Mini Frequency Inverter User Manual
103
Failur
e No
Failure
code
Failure description
Potential causes
Solutions
protection
Motor rotation is blocked or load
mutation occurs
Prevent the motor rotation from
blocking and reduce the load
mutation
Common motor maintains running
under heavy load for a long period of
time
Replace the common motor with
variable frequency
motor or
improve the running frequency
Motor overload protection time is set
too small
Increase the motor overload
protection time
V/F curve ratio is set too large
Adjust V/F curve setting and
torque increment
DC braking current is set too high
Reduce the DC brake current
20
LP
Input power failure
There is abnormal connection,
missing connection or disconnection
at the power terminal of the inverter
Check the power connections as
per the operational regulations
and eliminate the errors of
missing connection and
disconnection
21
SP
Abnormal output
phase loss
There is abnormal connection,
missing connection or disconnection
at the output side of the inverter
Check the power connections at
the output side of the inverter as
per the operational regulations
and eliminate the errors of
missing connection and
disconnection
22
ER01
EEPROM failure
EEPROM reading and writing failure
Seek for technical support
23
ER02
CPU failure
CPU failure
Seek for technical support
24
ER03
Keypad
communication
fault
Keypad or its control line
failure;
Check the connection of
Keypad
and its control line.
CPU failure
Seek for technical support
25
ER04
Parameter setting
failure
In
traverse
or
three-wire
operation
mode,
wrong
parameter setting
Modify parameter setting
26
ER05
Communication
abnormal 2
(Terminal 485)
The communication of terminal 485
is disconnected
Check the connection of the
equipment communications
The baud rate is set improperly
Set compatible baud rate
The communication of terminal 485
is faulty
Check whether the data receiving
and transmission complies with
the protocol, whether the check
sum is correct and whether the
receiving
and
transmission
interval
complies
with
the
requirements
The communication of terminal 485
is time-out
Check
whether
the
communication timeout is set
properly
and
confirm
the
communication
cycle
of
the
application program
The failure alarm parameter is set
improperly
Adjust the failure alarm parameter