HV350 Mini Frequency Inverter User Manual
44
9: 8,N,2 for RTU
(
MODBUS
)
MASTER
PC.02
Local address
1~32
,
0 is the broadcast address
1
216
+
PC.03
Communication
timeout detect
0
,
No detection
2.0~10.0s
0
217
+
PC.04
Response delay
2~1000ms
218
+
PC.05
EEROM
Store
selection
0
:Store
1
:
no store function
0
219
+
Pd Group
Faults and protection parameters
Pd.00
Motor
overload
protection mode
0:
No protection
1:
Common motor protection
2:
Variable frequency motor protection
1
220
+
Pd.01
Motor
overload
protection factor
20.0~150.0%
100.0
221
+
Pd.02
Over
voltage
stall
selection
0: Disabled
1: Enabled
1
222
+
Pd.03
Stall
over
voltage
point
120.0~150.0%
120.0
223
+
Pd.04
Selection of overload
pre-alarm detection
0: Detect at constant speed and alarm
1: Detect all the time and alarm
0
224
+
Pd.05
Overload
detection
threshold
20.0~180.0%
150.0
225
+
Pd.06
Overload
pre-alarm
delay
0.0~60.0s
2.0
226
+
Pd.07
Auto current limiting
threshold
20.0~180.0%
150.0
227
+
Pd.08
Frequency
decrease
rate
during
current
limiting
0.00~99.99 Hz/s
0.00
228
+
Pd.09
Action mode of auto
current limiting
0: Disabled
1: Enabled during Acc/Dec, disabled at
1
229
+