81 ARMING OPTIONS
811 Final Door
812 Exit Flt Bell
813 Line Flt Bell
814 Inhib Tamper
815 Forced Arm
816 Dpy Armed
818 Rearm Always
819 Rearm Count
817 Ext. Blk Exit
81 10 Arm Squawk
81 11 Infinite Exit
Used to select options for arming the panel.
Final Door
when selected will terminate the exit buzzer 6
seconds after all exit routes and access routes have closed
Exit Flt Bell
when enabled will trip the internal bell output in
the event of an exit fault e.g. if an E/E zone is still open at the
end of exit time.
Line Flt Bell
when enabled will trip the strobe, internal &
external bell outputs in the event of a line fault (when the
system is Armed).
Inhib Tamper
when enabled allows the user to inhibit tampers.
Forced Arm
, when enabled, allows the user to inhibit all open
inputs using ** and all open tampers (if
Inhib Tamper
is
enabled) using ##.
Dpy Armed
when enabled will display
System Armed
when
the panel is armed otherwise only date and time will be
displayed.
Ext. Blk Exit
; normally the Common Area (i.e. Block 0)
immediately arms when all the other blocks are armed i.e.
arms simultaneously with the last block. With
Ext. Blk Exit
set
to YES the system exit time is added to the final block’s exit
time giving the user more time to vacate.
If
Rearm Always
is enabled then the panel will always rearm
after an alarm activation when the panel is armed i.e. the
sounders will re-trigger each time a new activation occurs.
Rearm Count
is the number of times the panel will rearm if
Rearm Always
is not enabled. Note:
the sounders will re-
trigger as many times as the rearm count is set for.
Arm Squawk
, when enabled, briefly makes the internal bell
squawk and flashes the strobe when the system is fully armed
or set.
Note:
This feature overrides the RF-Keyfob Arm Squawk setting.
Infinite Exit Time
, when enabled, overrides the Full Set Exit
Time - it becomes infinite. The Exit Time only stops when an
Exit Terminator zone closes. This would typically be something
like a roller shutter or external push button. Arming can also be
terminated with the “Final Door” option and the shunt lock zone
closing.
System Options Menu
!
80
Default Eng. Code - 4567 Default User Code - 1111 (Irl) 1234 (UK)