11.2 External control signal 0…10 V to regulate start-up and power modulation of each boiler
Each boiler can receive and process an external signal 0…10 V.
The external signal 0…10 V will transmit to the boiler a set-up temperature value.
The signal 0…10 V must be connected to the terminals shown inside the boiler.
The linear characteristic is defined by 2 fixed points. The setting uses 2 pairs of
parameters for function value and voltage value
(F1/U1 and F2/U2).
Voltage
0,15V
U1=0V
U2=10V
Flow
temperature
setpoint
F2=85ºC
F2=65ºC
These are the predefined 0...10 V values in
configuration
:
These are the setpoints that we get from 0...10 V demand:
Voltage (V)
Setpoint (ºC)
1
22
2
29
3
36
4
43
5
50
6
57
7
64
8
71
9
78
10
85
Line nr.
predefined
F1
Function value 1
5954
150 (15ºC)
F2
Function value 2
5956
850 (85ºC)
U1
Voltage value 1
5953
0
U2
Voltage value 2
5955
10