ADI CD Boiler – Technical Manual
21
Press the control knob for 3 seconds to exit. The start page opens.
Setting of boiler flow temperature – Setpoint
On the navigation bar, turn the control knob until “
Service/setting pages
”
is preselected. Press the control
knob to enter to the page. In the work area, turn the control knob until operation object “
Expert
” is preselected.
Press the control knob and the login dialog box opens.
The user level setting is preselected. The Press the control knob. The user level is selected and is displayed
inverted. Turn the control knob to select “
Commissining
”. Press control knob to confirm selection. Message of
successful login opens and “
Continue
” is preselected. Press the control knob to confirm.
On the navigation bar, turn the control knob until “
Adjust/repair Page
”
is preseleted. Press the control knob
and the page opens. “
Complete parameter list
” is preselected. Press the control knob and the complete
parameter list opens.
The title of the first parameter list page is preselected. Press the control knob. Turn the control knob until the
title “
Consumer circuit 1
” is preselected. Press the control knob. Turn the control knob until parameter “
1859
Flow temp setp cons request
” is preselected. Press the control and the value is selected. Turn the control
knob to set the value and press the control knob to confim.
Press the control knob for 5 seconds to exit. Press the control knob and the start page opens
Summary of Contents for ADISA ADI CD 105
Page 1: ...TECHNICAL MANUAL OF INSTALLATION USE AND MAINTENANCE 4 2020 uk ADI CD CONDENSING BOILER...
Page 7: ...ADI CD Boiler Technical Manual 7 Models ADI CD 200 and higher...
Page 31: ...ADI CD Boiler Technical Manual 31 12 1 Electric drawing ADI CD 70 750...
Page 32: ...ADI CD Boiler Technical Manual 32 12 2 Electric drawing ADI CD 850 950...
Page 69: ...www adisaheating com ADISA HEATING HIPLUS AIRE ACONDICIONADO S L...