ADI CD Boiler – Technical Manual
60
18.4.2 Change of fuel: from Propane gas to Natural gas
In order to change fuel, it is enough
-
Re-programm the Siemens controller
-
to adjust the boiler combustion with the new fuel to the correct parameters, either for Natural
Gas or for Propane Gas.
-
Change or update identification plate for the new gas
The process is the same if you have to change from natural gas to propane.
Note: just available for models with power output lower than 500 kW.
Datos para potencia máxima:
Model
Power output
Power Input
LPG Max
LPG Max
kW
kW
m3/h
kg/h
CD 70
70,5
72,7
3,0
6,0
CD 85
85
87,7
3,7
7,2
CD 105
104
107,2
4,5
8,8
CD 120
120
123,5
5,1
10,2
CD 175
161,8
166,0
6,9
13,7
CD 200
197,5
202,2
8,4
16,7
CD 250
241
246,5
10,3
20,4
CD 325
294
300,5
12,5
24,8
CD 375
354
361,2
15,1
29,8
CD 450
440
448,2
18,7
37,0
CD 550
530
546,4
22,8
45,1
LGP (Propane gas) :
LCV: 23,98 kW/m3
Density: 1,98 kg/m3
Summary of Contents for ADISA ADI CD 105
Page 1: ...TECHNICAL MANUAL OF INSTALLATION USE AND MAINTENANCE 4 2020 uk ADI CD CONDENSING BOILER...
Page 7: ...ADI CD Boiler Technical Manual 7 Models ADI CD 200 and higher...
Page 31: ...ADI CD Boiler Technical Manual 31 12 1 Electric drawing ADI CD 70 750...
Page 32: ...ADI CD Boiler Technical Manual 32 12 2 Electric drawing ADI CD 850 950...
Page 69: ...www adisaheating com ADISA HEATING HIPLUS AIRE ACONDICIONADO S L...