ERROR
CODE
DESCRIPTION OF ERROR - TEXT
DIAGNOSTIC
CODE
DIAGNOSTIC
122
Flow temp HC2 not reached
Check installation and components
125
Maximum boiler temperature exceeded
501-502
Supervision exceeded, no temperature modification after flame
126
DHW charging temperature not reached
Check installation and components
127
DHW legionella temperature not reached
Check installation and components
128
Loss of flame in operation
394
Check electric supply, polarity and ionization electrode
128
Loss of flame in operation, counter exceeded
625
Check electric supply, polarity and ionization electrode
130
Flue gas temperature max. limit exceeded
Check sensor, connection and chimney
132
Gas pressure switch safety shut-down
409
Insufficient gas supply, check gas pressure
133
Safety time for establishment of flame exceeded
625
Check electric supply, polarity and ionization electrode
151
BMU fault internal
Check parameters, call technical service
152
Parameterization error
781
9525 LF > 9530 HF. Check burner revolutions
152
Parameterization error
782
9513 ignition > 9530 HF. Check burner revolutions
152
Parameterization error
575
9612 GP configuration - H6 6008 double function. Check parametrization
152
Parameterization error
576
9611 LP configuration - H7 6011 double function. Check parametrization
152
Parameterization error
Others
Call technical service for diagnostic code
153
Unit manually locked
-
160
Fan fault
380
Fan speed thershold not reached. Faulty fan, bad adjustments, check connections
164
Flow/pressure switch HC fault
562
Check water pressure, fill circuit, check electric terminal
183
Unit in parameterization mode
-
260
Flow temperature 3 sensor fault
Short circuit or Open circuit flow sensor B14. Check connection and component
317
Mains frequency outside permissible range
Check correct electric supply in boiler terminals
324
Same sensor Input BX
Check configuration in parameters list
325
Same sensor Input BX/extension module
Check configuration in parameters list
326
Same sensor Input BX/mixing valve group
Check configuration in parameters list
327
Same function mixing valve group
Check configuration in parameters list
328
Same function mixing valve group
Check configuration in parameters list
329
Same funct ext module/mixing valve group
Check configuration in parameters list
330
Sensor input BX1 no function
Connect temperature sensor in BX terminal
331
Sensor input BX2 no function
Connect temperature sensor in BX terminal
332
Sensor input BX3 no function
Connect temperature sensor in BX terminal
335
Sensor input BX21 no function (any extension module)
Connect temperature sensor in BX terminal
336
Sensor input BX22 no function (any extension module)
Connect temperature sensor in BX terminal
339
Collector pump Q5 missing
Check connection and component
341
Collector sensor B6 missing
Check connection and component
Summary of Contents for ADISA ADI CD 105
Page 1: ...TECHNICAL MANUAL OF INSTALLATION USE AND MAINTENANCE 4 2020 uk ADI CD CONDENSING BOILER...
Page 7: ...ADI CD Boiler Technical Manual 7 Models ADI CD 200 and higher...
Page 31: ...ADI CD Boiler Technical Manual 31 12 1 Electric drawing ADI CD 70 750...
Page 32: ...ADI CD Boiler Technical Manual 32 12 2 Electric drawing ADI CD 850 950...
Page 69: ...www adisaheating com ADISA HEATING HIPLUS AIRE ACONDICIONADO S L...