ADI CD Boiler – Technical Manual
37
Summer/winter heating limit
The summer/winter heating limit is used to switch the heating on and off in the course of the year, depending on
the outside temperature. In Automatic operation, switching on/off takes place automatically, so there is no need
for the user to do this manually.
The Summer/winter changeover function switches the heating off when the attenuated outside temperature
exceeds the adjusted changeover temperature, in the last 24 hours. The heating system is switched on again
(winter mode) when the attenuated outside temperature drops 1 ºC below the adjusted value.
730 / 1030 1330
°C
730 / 1030 / 1330 +1 °C
730 / 1030 / 1330 -1 °C