1-71
TROUBLESHOOTING
“RUN” light flickers and “ALARM” is indicated on the remote control switch.
The unit No., alarm code and the unit code is alternately indicated on the set temperature section,
and the unit No. and alarm code are indicated on the display of the outdoor unit PCB.
In case that the abnormality of alarm code 51, 52, 53 or 54 occurs three times within 30 seconds, the
alarm code of abnormality occurred for the third time is indicated. Retry operation is performed up to
second time of abnormality occurrence.
Conditions:
Inverter current with 105% of the rated current, (1) runs continuously for 30 seconds or
(2) runs intermittently and the accumulated time reaches up to 3.5 minutes, in 10 minutes.
*1): Regarding replacing or the checking of ISPM, refer to page 1-114 regarding electrical discharge.
Alarm
Code
Protection Activation Against Instantaneous Overcurrent of Inverter (1)
(For 24 and 30HP)
Refer to next page.
Restart operation.
No
Smaller than
activation current.
Yes
(ISPM is normal.)
Is discharge pressure
high?
Check pressure and
refrigeration cycle.
Is the compressor
current larger than
activation current?
Check the inverter
circuit board (ISPM)
connection. *1)
Normal
"2"
"4"
Check for clogging of
the heat exchanger.
Check the fan motor.
Replace ISPM.
Abnormal
Connect it correctly.
ISPM is faulty.
Replace it.
Is the cause of
stoppage "
" of
troubleshooting by
7-segments display
"2" or "4"?
220V 60Hz
14.0A
27.5A
380-415V 50Hz
380V 60Hz
Power Supply
Activation Current
380-415V 50Hz
380V 60Hz
220V 60Hz
RAS-24FSG1, RAS-30FSG1, RAS-24FS5, RAS-30FS5
Model
14.0 / 27.5
Rated Current