1-41
TROUBLESHOOTING
“RUN” light flickers and “ALARM” is indicated on the remote control switch.
The unit No., alarm code and the unit code is alternately indicated on the set temperature section,
and the unit No. and alarm code are indicated on the display of the outdoor unit PCB.
This alarm is indicated when the following conditions occurs three times within one hour;
(1) The temperature of the thermistor on the top of the compressor is maintained higher than 132
°
C
for 10 minutes, or (2) The temperature of the thermistor on the top of the compressor is maintained
higher than 140
°
C for 5 seconds.
Alarm
Code
Excessively High Discharge Gas Temperature
at the Top of Compressor Chamber
Is the thermistor on
top of compressor
good?
Yes
Check the outdoor unit
PCB if the compressor
discharge gas
temperature is over
132
o
C.
Remove sudden
changes of load like
short path of discharge
air to the intake of the
outdoor unit, or the
cause of frequent
thermo-ON/OFF.
Remove sudden
changes of load
like short path of
discharge air to the
air intake of the
outdoor unit, or the
cause of frequent
thermo-ON/OFF.
Faulty Thermistor
See page 1-53 for the
thermistor resistance.
No
No
No
Is the thermistor
installed correctly
on the compressor?
Yes
Install it correctly.
No
Is it at cooling or
heating mode when the
alarm has occurred?
Is the opening degree
of ex. valve of outdoor
bypass 100%?
Is the connector
(CN12) for ex. valve
of outdoor bypass
connected properly?
Is the opening of all
the operating indoor
units ex. valve 100%?
Is the amount of
refrigerant correct?
Is gas leaking?
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Cooling
Check the outdoor unit
PCB to see if the
compressor discharge
gas temperature is
over 132
o
C.
Heating Operation
Cooling Operation
Heating
No
Plug the connectors
(*1) of PCB1
properly.
No
Charge correct
refrigerant volume.
Refer to TCII.
No
Check the ex.
valve.
No
Plug the connector
CN12 of PCB1
properly.
No
No
Remove sudden
changes of indoor load
(short path, etc.) or
short path of air
between outdoor units.
Repair leaks of gas.
Recharge refrigerant.
No
Is the opening of the
outdoor unit ex. valve
100%?
<FX Series Only>
Are the connectors
(*1) of PCB1 of the
outdoor unit heat
exchanger's ex. valve
connected properly?
Yes
Position of Thermistor
THM8 (Td1)
for Inverter Drive
RAS-5FSG, RAS-5FS3
THM8 (Td1)
for Inverter
Drive
RAS-8FSG, RAS-8FS3
RAS-10FSG, RAS-10FS3
RAS-8FXG, RAS-8FX3
RAS-10FXG, RAS-10FX3
THM9 (Td2)
for Constant
Speed Drive
THM8 (Td1)
for Inverter
Drive
RAS-16FSG, RAS-16FS3
THM9 (Td2)
RAS-20FSG,
RAS-20FS3
RAS-24FSG1,
RAS-24FS5,
RAS-30FSG1,
RAS-30FS5
THM12 (Td3)
THM13 (Td4)
20, 24, 30HP
only
for Constant Speed Drive
5 to 20HP
24 and 30HP
CN10 and CN11
CN10, CN11,
CN12 and CN20
*1): PCB1 Connector No. is
shown in the below table.