3-1
MAIN PARTS
3.
MAIN PARTS
3.1
Inverter
3.1.1 Specifications of Inverter (For 380/415V, 50Hz and 380V, 60Hz Power Source)
RAS-24FSG1, RAS-24FS5,
RAS-30FSG1, RAS-30FS5
14.0A
Vector PWM Control
30 to 115Hz
0.01Hz, at
Applicable Frequency Range
Excessive High or
Low Voltage for Inverter
Abnormality of
Current Sensor
Cause of Abnormality:
Failure of Current Sensor
Failure of Transistor Module
Failure of ISPM
Failure of Compressor
Disconnected Wiring
Stoppage at a current of compressor smaller than 0.5A
When the frequency is 15 to 18Hz after starting.
Refer to the note in next page.
RAS-5FSG, RAS-5FS3, RAS-8FSG,
RAS-8FS3, RAS-10FSG, RAS-10FS3,
RAS-16FSG, RAS-16FS3, RAS-20FSG,
RAS-20FS3, RAS-8FXG, RAS-8FX3,
RAS-10FXG, RAS-10FX3
Conditions:
1. Power Source Voltage AC380/415V
2. Non-Loading (Free Output)
3. Ammeter Type Volt-Meter (X1.1)
Excessive Low Voltage at a DC Voltage is Lower than 350V
Excessive High Voltage at a DC Voltage is Higher than 750V
+ 10% at Applicable Frequency Range
0.5Hz/S, 1Hz/S, 3Hz/S, 6Hz/S, 30Hz/S (5 Steps)
Frequency < 75Hz, Space Vector PWM Control
75Hz < Frequency < 115Hz, V/F Control
30 to 95Hz (5HP),
30 to 115Hz (8 to 20HP)
Control Method
Output / Characteristics
Applicable Model
Applicable Power Source
Output Voltage (Maximum)
Output Current (Maximum)
Accuracy of Output Voltage
Protection Function
0.005Hz, at
Applicable Frequency Range
14.0A (5, 8 and 10HP),
16.5A (16 and 20HP)
3 Phase 380/415V + 10% 50/60Hz +5%
380/415V, 3 Phase
Continuous
Soft Start Stop
Time Rating
Range Output Frequency
Accuracy of Frequency
(V)
400
380
300
200
100
0
50
75
100
115
24 and 30HP
f (Hz)