1-101
TROUBLESHOOTING
b. Inverter Printed Circuit Board: PCB3
•
Dip Switch and LED Functions on Outdoor Unit Inverter Printed Circuit Board
*: Applied to the following products;
1) RAS-8 to 20FSG/FS3
380-415V, 50Hz Model and 380V, 60Hz Model (After Manufacturing # U4NG1002)
220V, 60Hz Model (From The First Production)
2) RAS-5FSG/FS3
380-415V, 50Hz Model and 380V, 60Hz Model (After Manufacturing # U4MV0197)
3) RAS-8, 10FXG/FX3
From First Production
Switch Name
DSW1
Normal:
No.1 and No.2 of DSW1 are OFF.
Emergency Operation or Troubleshooting:
No.1 of DSW1 is ON.
No.2 of DSW1 is OFF.
The above setting aims not to trip even if the CT detects 0A.
Name of Printed
Circuit Board
LED1 (Red)
This indicates the state of transmission.
Flickering: Normal Transmission
Activated or Deactivated: Abnormality in Transmission Circuit
* LED2 (Red)
This indicates the voltage between both terminal of capacitor
CB1 and CB2 for inverter part.
Activated:
The voltage between both terminals of capacitor,
CB is 50V
+
20V or greater.
Deactivated:
The voltage between both terminals of capacitor,
CB is 50V
+
20V or smaller.
Function
Function
ON
OFF
LED2
DSW1
LED1