TROUBLESHOOTING
“RUN” light flickers and “ALARM” is indicated on the remote control switch.
The unit No., alarm code and the unit code is alternately indicated on the set temperature section,
and the alarm code is indicated on the display of the outdoor unit PCB.
This alarm code is indicated when voltage between terminal “P” and “N” of inverter module (ISPM) is
insufficient and its occurrence is three times in 30 minutes. In the case that the occurrence is smaller
than 2 times, retry is performed.
Alarm
Code
Excessively Low or High Voltage for Inverter (For 24 and 30HP)
TB3
+
-
N
P
Direct Current
Measuring Position
Measuring Range: DC1000V
R
S
W
RB
V
T
U
N
PD
P
TB2
R216
R215
ZN20
LED201
ZN202
R201
R200
CN207
CN206
CN9
PC207
C
PC208
CN8
RB
N
P
P1
*1): If capacitor has high voltage, perform the high voltage
discharge work refer to item 1.3.6.
*2): Checking procedures of ISPM is indicated in item 1.3.6.
Does the voltage
fall during operation
by operation of
other apparatus?
Is connection
correctly between
ISPM and capacitors
(CB1 and CB2), DCL
or CMC?
Check capacitors
(CB1, 2).
Restart operation.
Check wiring and
cable capacity.
Connect correctly.
Replace capacitors.
Faulty ISPM.
Replace it.
Capacitors have high voltage.
Be careful especially. *1)
Yes
Yes
Yes
Check the wiring, ISPM
and CB. *2)
In case the wiring is
correct, replace ISPM.
Normal
Fault
(Loose Wiring,
Change of
Color)
Check Item
Frequency can
increase higher
than 60Hz.
Compressor
stops immediately.
(lower than 20Hz)
Compressor stops
when frequency
increase. (Approx.
20Hz to 60Hz)
How is
compressor
operation?
Yes
Is the DC voltage
over 460V?
Yes
* Be careful especially because of high voltage.
Yes
No
No
No
No
No
No
* In case of 380-415V/50Hz, 380V/60Hz:
Is the voltage over 323V during operation?
* In case of 220V/60Hz:
Is the voltage over 170V during operation?
Faulty ISPM.
Replace it.
220V/60Hz
460V
230V
380-415V/50Hz
380V/60Hz
Power Supply
Voltage (DC)
* In case of 380-415V/50Hz, 380V/60Hz:
Is the power supply voltage
380V 10% or 415V 10%?
* In case of 220V/60Hz:
Is the power supply voltage 220V 10%?
+
_
+
_
+
_
Does LED201 on
ISPM ON?