1-33
TROUBLESHOOTING
Is LED3 (yellow) on
PCB1' flickering more than
once in 10 seconds?
Is PCB1' setting
Non-pole operating.
*3)
No
Is LED2 (yellow)
on PCB(1) flickering
more than once in
10 seconds?
Is LED2 (yellow)
on PCB(1) ON?
Is LED3 on
PCB1' ON?
Faulty PCB(1)
Yes
Yes
Yes
Does Alarm occur with
all indoor units?
Yes
Yes
Connect CN8 of
PCB(1).
Faulty PCB(1)
Faulty PCB1
Set it correctly.
Faulty PCB1'.
No
No
Check wiring between
outdoor unit and indoor
units or fuse (EF1) for
PCB1'.
Yes
No
Does refrigeration system
setting between DSW1
on PCB1' and DSW5
on PCB1' correspond?
No
Indoor
Unit
No
No
Are other units in
same condition?
Yes
Check other indoor units.
Set correctly.
No
Faulty PCB1'.
Is LED3 (yellow)
ON even if CN2 of
PCB1' is removed?
Yes
Yes
No
CH
Unit
*1): PCB1 Factory Setting for Non-Pole Transmitting
*2): In case that terminal resistance (DSW10-1P) is OFF when H-Link Connection is performed.
Set the terminal resistance to ON when CN2 is removed.
Set the terminal resistance to OFF when CN2 is reconnected.
*3): PCB1' Factory Setting for Non-Pole Transmitting
Item
Setting Position
SW1
Right Side (New Transmission Side)
DSW9-2P
ON
DSW10-1P
ON
CN101
Transmission Wire Connecting
CN19
Non-Occupied
Check Item
Item
Setting Position
Power Supply
Faston Terminal
SW2
Left Side (New Transmission Side)
380-415V/50Hz
JP1
Short Circuited
380V/60Hz
CN2
Transmission Wire Connecting
220V/60Hz
between R1 and S1
CN18
Non-Occupied
between R1 and N