2-14
SERVICING
(2.1 Outdoor Unit)
TURN OFF all power source switches.
Adjustable Wrench or Spanner,
Phillips Screwdriver
Tool
(10) Remove three nuts fixing the compressor and remove the compressor.
There is no nut at the left rear side.
NOTES:
1. Pull out the compressor without removing the oil heater.
Remove the oil heater after the compressor is put outside the unit. (Constant Comp. Only)
2. When lifting the compressor, hold the discharge pipe vertically and turn it to the left and pull the
compressor towards the front side by paying attention to the compressor leg not to touch the
suction pipe.
(11) Regarding remounting the compressor work, perform the above work in the reverse processes.
Front Side
Special Nut
Lift and move
towards left
Pull out towards
front side.
Vibration-proof Rubber
Suction Pipe
Pay attention to
this part not to touch
the compressor leg.