2-47
SERVICING
(2.2 In-the-Ceiling Type)
2.2.5 Removing Electronic Expansion Valve Coil
(1) Remove the service cover according to the item 2.2.4 “Removing Thermistor for Liquid Piping and
Gas Piping”.
(2) The following procedures are the same
with other models.
Phillips Screwdriver
Tool
Phillips Screwdriver, Spanner
Tool
2.2.6 Removing Float Switch
(1) Remove the service cover according to the item 2.2.4 “Removing Thermistor for Liquid Piping and
Gas Piping”.
(2) The float switch is fixed on the heat exchanger fixing plate.
Remove the float switch by using two spanners.
ATTENTION:
When reassembling, handle the float switch carefully.
(Tightening Torque: Approx. 0.3N-m)
If the float switch is dropped, malfunction will occur.
TURN OFF all power source switches.
Float Switch