4-3
OPTIONAL FUNCTION
(4.1 Indoor Unit)
(3) Remote Control 3 (Pulse Signal Input)
By using the signal from a building management system, the air conditioners can be stopped.
If a signal is input during stoppage of air conditioner, the air conditioner remains unchanged.
The basic wiring and time chart are shown below.
Turn OFF the power source before setting the dip switch.
NOTES:
1. Picking up signal within 10 seconds after power supply is turned ON is not available due to initializing of
components.
Do not change the signal (RUN/STOP) in this period.
2. Remote Control Switch is required for this function.
OFF
X1
Power
Source
Control Circuit
Indoor Unit PCB
CN4
X1
3P Connector
2
1
2
1
NOTE:
The pulse width shall be wider than 200ms.
Wiring Diagram Example of Remote Control 3
1
Indoor Unit PCB
Set No.6 at ON side.
ON
OFF
2 3 4 5 6 7 8
DSW2
Signal to 1 & 2 of CN4