Technical data
64/75
11.1.2
netHOST for Real-Time Ethernet systems
NHST-T100-EN/PNM/ECM/EIM
Parameter
Value
Communication controller
Type
netX 100
Memory
RAM
8 MB SDRAM
FLASH
4 MB serial Flash
SD memory card
(optional)
max. 2 GByte
Do not use SDHC- or SDXC- card types
USB Interface
USB Socket
Mini-USB, 5-pin
Display
LEDs
SYS
system status netHOST
APL
application status netHOST
LINK
Link (LAN and RTE interface)
ACT
Activity (LAN and RTE interface)
Protocol specific
LEDs
:
PROFINET IO Controller:
SF
,
BF
EtherCAT Master:
RUN
,
ERR
Ethernet/IP Scanner:
MS
,
NS
Power supply
Voltage
24 V ± 6 V DC
with reverse voltage protection
Current at 24 V (typically) 130 mA
Power consumption
3.2 W
Connector
Mini-COMBICON, 2-pin
Power supply
For UL compliant usage:
Device shall be supplied by an isolated voltage source.
Environmental conditions
Temperature range
0 … + 60 °C
Humidity
No condensation permitted
Environment
For UL compliant usage:
Device must be used in a pollution degree 2
environment.
Device
Dimensions (L x W x H)
100 x 52 x 70 mm (without connector)
Weight
appr. 150 g
Mounting
on DIN rail EN 60715
Protection class
IP 20
RoHS
Yes
CE Sign
CE Sign
Yes
Emission
CISPR 11 Class A
Immunity
EN 61131-2:2003
Configuration
Software
SYCON.net
Ethernet Device Configuration Tool
Ethernet Interfaces
(RTE at X2 and LAN at X3)
Transmission rate
100 MBit/s
10 MBit/s
Interface type
100 BASE-TX, isolated
Half duplex/Full duplex
supported (at 100 MBit/s)
Auto-Negotiation
supported
Auto-Crossover
supported
Connector
X2 (RTE interface): 2 x RJ45
X3 (LAN interface): 1 x RJ45
Table 50: Technical data netHOST for Real-Time Ethernet systems
netHOST NHST-T100 | LAN controlled master devices
DOC130401UM05EN | Revision 5 | English | 2018-05 | Released | Public