Troubleshooting
51/75
9
Troubleshooting
There are two steps of error diagnosis:
·
the initial approximate diagnosis by checking the LEDs of the device,
·
the comprehensive diagnosis with the SYCON.net configuration and
diagnosis software via LAN connection.
The following overview describes the error conditions that may be detected
by checking the LEDs (for identification of the LEDs, please refer to section
Positions of the LEDs, connectors and control elements
page 31]).
For information on how to diagnose the netHOST device with
SYCON.net, see Operating Instruction Manual
Configuration of LAN
controlled master devices
–
netHOST
, DOC130402OIxxEN, stored
on the netHOST Solutions DVD in the
Documentation\english
\1.Software\SYCON.net
directory.
LED
LED state
Cause/remedy
All
No LED is on
The device is not powered or the device is
defective and needs replacement.
SYS
RTE devices: position
(4)
Fieldbus devices: position
(5)
SYS
LED flashes
yellow/
green at 1 Hz
After a power cycle the device has not found a
valid firmware and remains in boot loader mode.
The firmware of the device has to be “recovered”.
See chapter
If recovery fails, the load memory of the device
might be defective.
SYS
RTE devices: position
(4)
Fieldbus devices: position
(5)
SYS
LED flashes
yellow
The device could not be initialized. No boot loader
was found in the load memory. The load memory of
the device might be defective or a USB cable,
which has pin 4 connected with ground, might be
attached to the device. This prevents the device
from starting.
SYS
RTE devices: position
(4)
Fieldbus devices: position
(5)
SYS
LED shows static
yellow
The hardware of the device is defective and needs
replacement.
SYS
RTE devices: position
(4)
Fieldbus devices: position
(5)
APL
RTE devices: position
(5)
Fieldbus devices: position
(6)
SYS
LED shows static
green
and
APL
LED flashes
red or
shows static
red.
The device is well initialized. Further diagnosis is
possible with the
APL
LED. See section
APL
RTE devices: position
(5)
Fieldbus devices: position
(6)
APL
LED flashes
green.
The communication at port X2 or/and port X3 is not
in data exchange mode. See also section
Table 33: netHOST troubleshooting by LED
For protocol-specific error diagnostics by LED, see section
Fieldbus and Real-Time Ethernet systems
netHOST NHST-T100 | LAN controlled master devices
DOC130401UM05EN | Revision 5 | English | 2018-05 | Released | Public